Parallel Operation of D.C. Generators
Parallel Operation of D.C. Generators
In a d.c. power plant, power is usually
supplied from several generators of small ratings connected in parallel
instead of from one large generator. This is due to the following
reasons:
(i) Continuity of service
If a single large generator is used in the power plant, then in case of its breakdown, the whole plant will be shut down. However, if power is supplied from a number of small units operating in parallel, then in case of failure of one unit, the continuity of supply can be maintained by other healthy units.
(ii) Efficiency
Generators run most efficiently when loaded to their rated capacity. Electric power costs less per kWh when the generator producing it is efficiently loaded. Therefore, when load demand on power plant decreases, one or more generators can be shut down and the remaining units can be efficiently loaded.
(iii) Maintenance and repair
Generators generally require routine-maintenance and repair. Therefore, if generators are operated in parallel, the routine or emergency operations can be performed by isolating the affected generator while load is being supplied by other units. This leads to both safety and economy.
(iv) Increasing plant capacity
In the modern world of increasing population, the use of electricity is continuously increasing. When added capacity is required, the new unit can be simply paralleled with the old units.
(v) Non-availability of single large unit
In many situations, a single unit of desired large capacity may not be available. In that case a number of smaller units can be operated in parallel to meet the load requirement. Generally a single large unit is more expensive.
(i) Continuity of service
If a single large generator is used in the power plant, then in case of its breakdown, the whole plant will be shut down. However, if power is supplied from a number of small units operating in parallel, then in case of failure of one unit, the continuity of supply can be maintained by other healthy units.
(ii) Efficiency
Generators run most efficiently when loaded to their rated capacity. Electric power costs less per kWh when the generator producing it is efficiently loaded. Therefore, when load demand on power plant decreases, one or more generators can be shut down and the remaining units can be efficiently loaded.
(iii) Maintenance and repair
Generators generally require routine-maintenance and repair. Therefore, if generators are operated in parallel, the routine or emergency operations can be performed by isolating the affected generator while load is being supplied by other units. This leads to both safety and economy.
(iv) Increasing plant capacity
In the modern world of increasing population, the use of electricity is continuously increasing. When added capacity is required, the new unit can be simply paralleled with the old units.
(v) Non-availability of single large unit
In many situations, a single unit of desired large capacity may not be available. In that case a number of smaller units can be operated in parallel to meet the load requirement. Generally a single large unit is more expensive.
Connecting Shunt Generators in Parallel
The generators in a power plant are
connected in parallel through bus-bars. The bus-bars are heavy thick
copper bars and they act as +ve and -ve terminals. The positive
terminals of the generators are .connected to the +ve side of bus-bars
and negative terminals to the negative side of bus-bars. Fig. (3.15)
shows shunt generator 1 connected to the bus-bars and supplying
load. When the load on the power plant increases beyond the capacity of this generator, the second shunt generator 2 is connected in parallel wish the first to meet the increased load demand. The procedure for paralleling generator 2 with generator 1 is as under:
load. When the load on the power plant increases beyond the capacity of this generator, the second shunt generator 2 is connected in parallel wish the first to meet the increased load demand. The procedure for paralleling generator 2 with generator 1 is as under:
(i) The prime mover of generator 2 is
brought up to the rated speed. Now switch S4 in the field circuit of the
generator 2 is closed.
(ii) Next circuit breaker CB-2 is closed
and the excitation of generator 2 is adjusted till it generates voltage
equal to the bus-bars voltage. This is indicated by voltmeter V2.
(iii) Now the generator 2 is ready to be
paralleled with generator 1. The main switch S3, is closed, thus
putting generator 2 in parallel with generator 1. Note that generator 2
is not supplying any load because its generated e.m.f. is equal to
bus-bars voltage. The generator is said to be “floating” (i.e., not
supplying any load) on the bus-bars.
(iv) If generator 2 is to deliver any
current, then its generated voltage E should be greater than the
bus-bars voltage V. In that case, current supplied by it is I = (E –
V)/Ra where Ra is the resistance of the armature circuit. By increasing
the field current (and hence induced e.m.f. E), the generator 2 can be
made to supply proper amount of load.
(v) The load may be shifted from one
shunt generator to another merely by adjusting the field excitation.
Thus if generator 1 is to be shut down, the whole load can be shifted
onto generator 2 provided it has the capacity to supply that load. In
that case, reduce the current supplied by generator 1 to zero (This will
be indicated by ammeter A1) open C.B.-1 and then open the main switch
S1.
Load Sharing
The load sharing between shunt
generators in parallel can be easily regulated because of their drooping
characteristics. The load may be shifted from one generator to another
merely by adjusting the field excitation. Let us discuss the load
sharing of two generators which have unequal no-load voltages.
Let E1, E2 = no-load voltages of the two generators
R1, R2 = their armature resistances
V = common terminal voltage (Bus-bars voltage)
Let E1, E2 = no-load voltages of the two generators
R1, R2 = their armature resistances
V = common terminal voltage (Bus-bars voltage)
I1 = (E1-V)/R1 and I2 = (E2 – V)/R2
Thus current output of the generators
depends upon the values of E1 and E3. These values may be changed by
field rheostats. The common terminal voltage (or bus-bars voltage) will
depend upon (i) the e.m.f.s of individual generators and (ii) the total
load current supplied. It is generally desired to keep the busbars
voltage constant. This can be achieved by adjusting the field
excitations of the generators operating in parallel.
Comments
Post a Comment